The A-ISOMETER® of the IRDH275 series is designed to monitor the insulation resistance of unearthed The IRDH275 automatically ad- apts itself to the .. DIN EN 61557-8: 1998-05. EN 61557-8: 1997-03, IEC 61557-8: 1997-02. ASTM F1669M-96, ASTM F1207M-96. Operating manual. TGH1361. Weight approx. 510 g.
View and Download Bender A-ISOMETER IRDH275 operating manual online. Insulation monitoring device for IT AC systems with galvanically connected rectifiers and converters and for IT DC systems. A-ISOMETER IRDH275 Measuring Instruments pdf manual download. Operating Manual A-ISOMETER®
Nominal frequency fn (for f< 50 Hz see characteristic curve in the manual). 0,1460 Hz. Nominal system voltage Un. DC 0650 V*. IRDH275-435: Supply voltage US (also see nameplate). AC 88264 V*. Frequency range US. 42460 Hz. Supply voltage US (also see nameplate). DC 77286 V*. IRDH275-427:.
9 Dec 2002 Power in electrical safety. Operating Manual. A-ISOMETER® IRDH575. Insulation monitoring for ungrounded AC and DC systems with integrated test generator and controller for. EDS46, EDS47 and EDS49 systems. Software version: D185 V1.6. TGH1364A / 4-2007
A latching setting ("fault memory") allows the device to reset automatically or require a manual re- set. An external and internal test/reset can be activated remotely or on the device. A comprehensive INFO menu displays additional information such as the system's leakage capacitance. The IRDH275 continuously monitors
28 Aug 2001 Power in electrical safety. Operating Manual. A-ISOMETER® IRDH275. IRDH275B. Insulation monitoring device for. IT AC systems with galvanically connected rectifiers and converters and for IT DC systems. Software version IRDH275: D160 V1.4. Software version IRDH275B: D159 V1.4. TGH1361en/
The ISOMETER® of the IRDH275 series is designed to monitor the insulation resistance of unearthed main circuits (IT systems) AC, AC / DC 0793 V resp. DC 0650 V. The AMPPlus measuring principle meets the particular requirements of modern power supplies which often include rectifiers, converters,
rage setting allows the device to reset automatically or require a manual reset. An exter- nal and internal test/reset can be activated remotely or on the device. A comprehensive. INFO menu displays additional information such as the current leakage capacitance. The IRDH275 continuously monitors the equipment ground
This document is intended as a reference guide for installing and using a BENDER IRDH275 ground fault detector. This document includes installation, setup, and usage instructions. For complete de- tails, including installation, setup, settings, and troubleshooting, refer to the IRDH275 user manual, document number
Type of enclosure. X112, free from halogen. DIN rail mounting acc. to. IEC 60715. Flammability class. UL94 V-0. Software version IRDH275. D160 V1.4. Software version IRDH275B. D159 V1.4. Operating manual. TGH1361. Weight approx. 510 g. Option "W". Shock resistance acc. to IEC 60068-2-27 (device in operation).